______________________________________________________ 
    10260 - 21 Street NW, Edmonton, Alberta, Canada T6P 1W4
Phone (780) 449-4777 Fax (780) 449-4766 E-mail duracool@compusmart.ab.ca

Alternative Refrigerant Reference Guide

Refrigerant Source Similar To Application ODP GWP1 Glide Components Lubricant Compatibility 2
DURACOOL 12aŽ Duracool Limited R 12 LMH 0.000 <3 6° F Hydrocarbon Blend AB,MO,PAG,POE
R 12 Many -- LM 1.000 6,650 0 °F 12 AB,MO,POE
R 134a Many R 12 MH 0.000 1,300 0° F 134a PAG,POE
DURACOOL 22aŽ Duracool Limited R 22 LMH 0.000 <3 0° F Hydrocarbon Blend AB,MO,PAG,POE
R 22 Many -- LMH 0.055 1,350 0 °F 22 AB,MO,POE
R 407C Many R 22 MH 0.000 1,5253 8 °F 32,125,134a POE
R 410A Allied R 22 MH 0.000 1,7253 <1 °F 32,125 POE
DURACOOL 502aŽ Duracool Limited R 502 LMH 0.000 <3 5 °F Hydrocarbon Blend AB,MO,PAG,POE
R 502 Many -- LM 0.330 (22)-1,3504 (115)-9,3004 <1 °F 22,115 AB,MO,POE
R 403B Isceon R 502 LM 0.025 (22)-1,3504 2.1° F 290,22,218 AB,MO,POE
R 404A Many R 502 LM 0.000 3,748 0.9 °F 125,143a,134a POE
R 407A ICI R 502 LM 0.000 1,7703 8.7 °F 32,125,134a POE
_________________________
1 GWP based on 100 year integration time horizon, defined in the Intergovernmental Panel for Climate Change (IPCC) Scientific Assessment 1994, CO2 = 1.
2 Modern Refrigeration and Air Conditioning 1996, The Goodheart-Wilcox Company, Inc., 362 p.
3 Climate Change 1995.
4 GWP of major component.